What the law states

Australian Building Code Paragraph 3.8.5.0 states:
Performance requirement P2.4.5 is satisfied for mechanical ventilation system if it is installed in accordance with AS 1668.2. "Mechanical ventilation for acceptable indoor air quality", except that any contaminated air from a sanitary
compartment or bathroom must:

(a) Exhaust directly to outside the building by way of ducts; or
(b) Exhaust into the roof space provided:

As detailed above, in dwellings with a metal roof, or where the roof is lined with sarking, ventilating directly in to the roof space is not permitted by building codes
unless the roof space is adequately ventilated by open eaves or roof vents.

The Manrose range offers many ducted solutions to exhaust to the outside through wall, roof or eaves to comply with the latest building code. Natural Ventilation for the above is acceptable as long as opening windows in each room have an area of 5% or more of the floor area of the room

Duct Standards

BCA Compliance to AS/NZ 1530 Part 3

Requirements are:

Internal Surface: Spread of flame not >0
Smoke Developed not >3
External Surface: Spread of flame not >7
Smoke developed not >5

AS/NZS 1530 Part 3
This is the Australian standard 1530, method for fire tests on building materials components and structures.

"Simultaneous determination of ignitability, flame propagation, heat release and smoke release"

AS1668 (summarised):
"...Buildings shall have a means of collecting or otherwise removing: cooking fumes and odours; steam from laundering, utensil washing, bathing and showering; odours from sanitary and waste storage spaces; poisonous or flammable fumes and gases..."

 
 

Bathrooms Bathrooms
The regulations require a fan capable of a minimum extraction capacity of 25 litres per second when installed

 

Toilets Toilets
The regulations require a fan capable of a minimum extraction capacity of 25 litres per second when installed

 

Kitchens Kitchens
The regulations require a fan capable of a minimum extraction capacity of 50 litres per second when installed

 

Laundries Laundries
The regulations require a fan capable of a minimum extraction capacity of 20 litres per second when installed